Commands on symbols

Let operators run a command by clicking a symbol: who may set it up, allowed commands, confirmation, feedback and protections.

A symbol on a process diagram card can send a command when an operator clicks it: click the pump to start it, right-click the valve to close it. Commands on symbols are set on the dashboard card that draws the diagram, so the same drawing can be clickable on a control-room board and read-only elsewhere.

Who may set it up

You needFor
Author commands on process diagram symbols (administrators by default)Adding or changing a command on a symbol. Without it, Run a command is not offered; existing commands keep their settings.
The right to change the boardSaving the card
The command’s own permissionPicking the command

Removing a symbol’s command, or saving a card without touching its symbol commands, does not need the authoring permission.

Which commands

Symbols send commands the same way as control cards: Send a command to a device, a command from the device profile’s catalogue of the Basic tier. Raw methods, privileged, critical and high-impact commands are refused on boards; send those from the device console. See Control cards and Sending commands to devices.

Add a command to a symbol

  1. Customise the board and open the Process diagram card’s settings (or Edit diagram for the full-screen editor, where the inspector’s Actions tab shows “Actions of “).
  2. In the actions, add a source: When a symbol is clicked, When a symbol is double-clicked or When a symbol is right-clicked.
  3. Choose the Symbol from the drawing’s symbols, by name, or Every symbol and thing (*).
  4. Add Run a command and pick the Device, the Command, the Control and the Value.
  5. Choose where parameter values come from: a fixed value, the board’s , or a value of the clicked symbol.
  6. Set Confirmation: Ask “Are you sure?” or Ask to type the command name. “A command from a symbol is always confirmed; the command itself can ask for more.”
  7. Select Save (the editor’s changes reach the card only when you apply them).

A symbol with an action shows a small dot in the editor (Has actions).

What the operator sees

  1. They click the symbol. A dialog “ on ” names the device, the command, the control and the value, for example “Pump 2: Start”. For an action on every symbol: “ (the same for every symbol)” with “It runs as set, not only on . Are you sure?”
  2. With a typed confirmation they type the command’s name.
  3. While it runs, the symbol shows a spinner in its bottom right corner (Command pending). A failure shows a red mark (Command failed).
  4. The reply is shown as text. A queued request shows “Sent; waiting for the device”. With no answer after 30 seconds the outcome is shown as unknown.

One command runs at a time per card: a click meanwhile is answered with “Another command of this diagram is still running; wait for its answer.”

Every run is written to the audit log with the symbol and the gesture (click, double-click or right-click).

Protections

RuleMessage
The symbol must exist in the drawing“A command is set on a symbol this process diagram does not have”
A symbol that has a command cannot be removed or renamed“A symbol that has a command cannot be removed or renamed; remove its command first”
Deleting a symbol in the editor drops its actions when you save“Deleting removes its N actions when you apply.”
An action that names a missing symbol is dropped“N actions name , which is not in the diagram; they are removed when you apply.”
A new symbol that takes a deleted symbol’s id does not inherit its actions—
Commands never run from a display screenControls and symbols are inactive there

Good practice

  • Give commands a clear label in the profile’s catalogue; the dialog shows it.
  • Use Ask to type the command name for anything that stops a process.
  • Show the result on the symbol: connect its Running or Opening field to the device value the command changes, so the picture shows what the device reports, not what was asked.
  • Keep a manual or local mode visible with a rule (Mode), so an operator sees when the equipment will ignore remote commands.