Debounce, hysteresis and dampening

Stop alarms from flapping – debounce by readings or device time, the clear margin, and dampening that holds a flapping alarm open.

A monitoring system that cries wolf is worse than none. Alarm rules have three settings against noise. Debounce makes a condition prove itself before the alarm opens or clears. Hysteresis puts a margin on the clear side. Dampening holds an alarm that keeps flipping.

Debounce

Field (JSON)Form labelRangeDefault
debounce.modeCount in: Readings in a row (count) or Seconds (device time) (duration)count
debounce.raiseRaise after this many readings in a row / Raise when true for (seconds)1 to 86,4001
debounce.clearClear after this many readings in a row / Clear when false for (seconds)1 to 86,4001

By readings

The alarm opens on the raise-th reading in a row whose condition is true, and clears on the clear-th reading in a row whose condition is false. One reading the other way resets the count. With the default 1 and 1, the alarm follows every reading.

Only readings that carry one of the rule’s keys count. A message with other keys is no reading for this rule.

By device time

The alarm opens when the condition has been true continuously for raise seconds, measured on the time stamps of the readings, not on the server’s clock. It clears symmetrically.

Important

The time only advances when a reading arrives. If a device reports every 10 minutes, “true for 60 seconds” is reached with the second true reading, 10 minutes later. If the device stops sending, nothing is decided until it sends again. Have devices repeat their state periodically, or use an offline alarm for silence.

Example: “door open for 120 s” is door_open == true with Seconds (device time), raise 120.

Severity changes

Inside an open alarm, a change of severity waits for the same debounce: a rise waits for the raise count or time, a fall waits for the clear count or time.

Hysteresis

hysteresis (form: Hysteresis (clear margin)) is an absolute number, 0 or more. It widens the threshold on the clear side of ordering comparisons (>, >=, <, <=):

ConditionHysteresisOpensClears
temperature > 803above 80at 77 or below
battery < 205below 20at 25 or above
pressure >= 60.2at 6 or abovebelow 5.8

Hysteresis does not apply to == and !=, and it is ignored when the rule has an explicit clear condition (that condition decides). A value hovering at the threshold therefore does not open and close the alarm on every reading.

Dampening

Dampening applies to every threshold rule. Without a dampening block, the defaults are used:

FieldMeaningRangeDefault
maxTransitionsOpens and clears allowed within the window2 to 1004
windowSecThe window10 to 86,400 s600
holdSecHow long the condition must stay clear before a held alarm clears1 to 86,400 s300

When a clear would make more than maxTransitions opens and clears within windowSec, the clear is held: the alarm stays open and is marked Flapping (timeline: Flapping: clears held back). It clears only after its condition has been clear for holdSec seconds of device time.

With the defaults: an alarm that opened and cleared twice in 10 minutes and opens a third time is held open on its next clear until the condition has been clear for 5 minutes.

Set your own values in JSON mode:

"dampening": { "maxTransitions": 6, "windowSec": 1800, "holdSec": 600 }

Worked examples

A noisy temperature probe. Readings every 10 s jump ±1 °C around 80.

"severities": [ { "severity": "MAJOR", "condition": { "key": "temperature", "op": ">", "value": 80 } } ],
"debounce": { "mode": "count", "raise": 3, "clear": 3 },
"hysteresis": 2

Opens on the third reading above 80 in a row, clears on the third reading at 78 or below in a row.

A door that may stand open briefly.

"severities": [ { "severity": "WARNING", "condition": { "key": "door_open", "op": "==", "value": true } } ],
"debounce": { "mode": "duration", "raise": 300, "clear": 1 }

Opens when the door has been open for 5 minutes by the device’s clock (the device must report while the door is open). In time mode a single reading never decides: the alarm clears with the second closed reading, at least 1 second after the first.

A pump that cycles on purpose. A rule on a pressure that drops every pump cycle would flap. Raise maxTransitions or holdSec so the expected cycling does not page, and keep the debounce short so a real fault is still seen quickly.

Choosing values

Device reportsSuggested debounce
Every few secondscount 3 to 5, or duration 30 to 60
Every minutecount 2 to 3
Every 10 to 60 minutescount 1 to 2. A duration rule takes at least one reporting interval.
Only on changecount 1; use the device’s own delay, or a Rules-card “stays so for” trigger