Translated from Türkçe by AI ·

Thanks a lot, Mr. Toprak. We added the integration to the node’s code and mounted it next to the transmitter with a stud. For five days the two lines have been almost on top of each other, and the node reads about 8% lower. The value is around 3 mm/s, below the threshold line, so I postponed the bearing replacement. One more note: on the first day the max had stuck in one aggregate, so the curve looked jagged.

♥ 1

Translated from Türkçe by AI ·

I found the intern’s code: vib = the largest absolute value of the samples from the last 1 second, in g. The transmitter’s label says “10-1000 Hz, mm/s RMS”.