This two-point calibration calculator finds slope = (eng₂ − eng₁) ÷ (raw₂ − raw₁) and offset = eng₁ − slope × raw₁. Counts of 819 and 4095 for 0 and 100 % give a slope of 0.0305 and an offset of −25.
- Engineering value
- –
- Raw value
- –
- Slope (gain)
- –
- Offset
- –
Engineering = slope × raw + offset.
Enter two points with different raw values and different engineering values.
How it works
How do you calculate slope and offset from two points?
Slope = (engineering 2 − engineering 1) ÷ (raw 2 − raw 1), and offset = engineering 1 − slope × raw 1. Then engineering = slope × raw + offset, and raw = (engineering − offset) ÷ slope.
Calibrating a sensor this way uses two reference readings, ideally near the ends of the range you care about. Values outside the two points are extrapolated on the same line.
Type in either the raw or the engineering field; the other follows.
In Hermetry A flow’s Scale block maps a raw range to an engineering range as readings arrive, for example 4–20 mA to 0–10 bar: Derived values.
Glossary Scaling (engineering units), Analog input, Sensor
Questions
Questions about the two-point calibration calculator
What are slope and offset?
The gain and zero of a linear sensor: engineering value = slope × raw + offset. Many devices and PLCs ask for exactly these two numbers.
Which two points should I use?
Two reference readings near the bottom and top of the range you measure, taken with a trusted instrument. The further apart they are, the smaller the effect of reading errors.