This 4–20 mA calculator scales linearly: value = low + (mA − 4) ÷ 16 × (high − low). 12 mA on a 0–10 bar transmitter reads 5 bar, and a loop below 3.8 mA usually means a sensor or wiring fault.
- Value
- –
- Share of the range
- – %
Within the signal range.Outside the signal range.Below 3.8 mA or above 20.5 mA: by a common convention this signals a fault in the sensor or the wiring, not a measurement.
Enter a signal and a range whose two ends differ.
How it works
How do you convert 4–20 mA to an engineering value?
Value = low + (signal − signal at 0 %) ÷ (signal span) × (high − low). For 4–20 mA the signal at 0 % is 4 mA and the span 16 mA, so 12 mA is half the range.
The other way, signal = signal at 0 % + (value − low) ÷ (high − low) × signal span. Type in either field and the other follows.
The 4 mA live zero lets you tell a reading at the bottom of the range from a broken wire, which reads 0 mA. Many systems treat a loop below 3.8 mA or above 20.5 mA as a fault.
In Hermetry In Hermetry a flow’s Scale block maps a 4–20 mA signal to its engineering range as readings arrive: Derived values.
Glossary Current loop (4–20 mA), Analog input, Scaling (engineering units)
Questions
Questions about the 4–20 mA calculator
Why does the signal start at 4 mA and not 0?
The live zero: 0 mA then means a broken wire or a dead transmitter rather than the bottom of the range, and the 4 mA also powers two-wire transmitters.
What do readings below 3.8 mA or above 20.5 mA mean?
By a common convention they are a fault signal from the transmitter or the wiring, not a measurement, and alarms treat them that way.