This power factor correction calculator uses Q = P × (tan φ₁ − tan φ₂): raising 100 kW from a power factor of 0.75 to 0.95 needs about 55 kvar and cuts the apparent power by 21 %.
- Capacitor bank needed
- – kvar
- Apparent power and current saved
- – %
- Apparent power now
- – kVA
- Apparent power after
- – kVA
- Reactive power now
- – kvar
- Reactive power after
- – kvar
Enter a power above zero and a target power factor higher than today’s, up to 1.
How it works
How many kvar do you need to correct the power factor?
The power factor is cos φ, so the reactive power is P × tan φ. The capacitors must supply the difference between the reactive power now and at the target: P × (tan φ₁ − tan φ₂).
Apparent power falls from P ÷ PF₁ to P ÷ PF₂, and the current with it, which frees capacity on cables and transformers.
Size the bank in steps with a controller where the load varies, and check harmonics: capacitors can resonate with harmonic currents.
In Hermetry Hermetry reads power factor from multifunction meters and can raise an alarm when it drops below a set value: Energy meter reading across sites.
Glossary Power factor, THD (total harmonic distortion)
Questions
Questions about the power factor correction calculator
Why correct to 0.95 rather than 1?
The last few hundredths cost the most capacitance, and a bank sized for 1.0 at full load overcorrects at light load. Many tariffs only charge below 0.9 to 0.95.
Does power factor correction save energy?
It mainly cuts reactive charges and current; the kWh the load uses stay the same. Lower current does reduce cable losses a little.