Cable voltage drop calculator

Free voltage drop calculator: the volts, percentage and power lost in a single- or three-phase copper or aluminium cable, from length, size and current.

This voltage drop calculator uses k × I × L × ρ ÷ A, with k = 2 for single phase and √3 for three phase: 32 A over 50 m of 6 mm² copper at 400 V drops 7.96 V, 1.99 %.

Voltage drop
– %
In volts
– V
Voltage at the load
– V
Power lost in the cable
– W
Resistivity used
– Ω·mm²/m

Resistance only: at large cross-sections the cable’s reactance adds to the drop.

How it works

How do you calculate cable voltage drop?

Drop = k × I × L × ρ ÷ A, with L the one-way length in metres, A the cross-section in mm² and k = 2 for single phase (out and back) or √3 for three phase (line to line).

ρ at 20 °C is 0.017241 Ω·mm²/m for copper and 0.028264 for aluminium. It rises by 0.393 % (copper) or 0.403 % (aluminium) per °C: a copper conductor at 70 °C has about 20 % more resistance.

This uses resistance only. For large cables and low power factors, the inductive reactance adds to the drop; use the cable maker’s tables there.

Questions

Questions about the voltage drop calculator

How much voltage drop is acceptable?

Many wiring rules limit it to around 3 % for lighting and 5 % for other loads, from the supply point to the load. Check the rule that applies where you install.

Which temperature should I use?

The conductor’s operating temperature: 70 °C for common PVC-insulated cables at full load, 90 °C for XLPE. 20 °C gives the lowest, best-case drop.