This voltage drop calculator uses k × I × L × ρ ÷ A, with k = 2 for single phase and √3 for three phase: 32 A over 50 m of 6 mm² copper at 400 V drops 7.96 V, 1.99 %.
- Voltage drop
- – %
- In volts
- – V
- Voltage at the load
- – V
- Power lost in the cable
- – W
- Resistivity used
- – Ω·mm²/m
Above 5 %: many wiring rules set limits around 3 to 5 %. Resistance only: at large cross-sections the cable’s reactance adds to the drop.
Enter a voltage and cross-section above zero, a length and current of 0 or more, and a temperature from −40 to 250 °C.
How it works
How do you calculate cable voltage drop?
Drop = k × I × L × ρ ÷ A, with L the one-way length in metres, A the cross-section in mm² and k = 2 for single phase (out and back) or √3 for three phase (line to line).
ρ at 20 °C is 0.017241 Ω·mm²/m for copper and 0.028264 for aluminium. It rises by 0.393 % (copper) or 0.403 % (aluminium) per °C: a copper conductor at 70 °C has about 20 % more resistance.
This uses resistance only. For large cables and low power factors, the inductive reactance adds to the drop; use the cable maker’s tables there.
Questions
Questions about the voltage drop calculator
How much voltage drop is acceptable?
Many wiring rules limit it to around 3 % for lighting and 5 % for other loads, from the supply point to the load. Check the rule that applies where you install.
Which temperature should I use?
The conductor’s operating temperature: 70 °C for common PVC-insulated cables at full load, 90 °C for XLPE. 20 °C gives the lowest, best-case drop.