This pipe head loss calculator uses Hazen–Williams, h = 10.67 × L × Q1.852 ÷ (C1.852 × d4.8704): 50 L/s through 1 km of 200 mm pipe with C = 130 moves at 1.59 m/s and loses 12.8 m of head.
- Velocity
- – m/s
- Head loss
- – m
- Per kilometre
- – m/km
- As pressure
- – bar
Above 2 m/s: losses, noise and surge risk grow quickly. Below 0.3 m/s: water ages and sediment settles. Hazen–Williams suits water at ordinary temperatures, in pipes of about 50 mm and up.
Enter a flow of 0 or more and a diameter, length and C above zero.
How it works
How do you calculate head loss in a water pipe?
Velocity = Q ÷ (π × d² ÷ 4), with Q in m³/s and d in metres: 50 L/s in a 200 mm pipe moves at 1.59 m/s.
Head loss (SI form of Hazen–Williams) = 10.67 × L × Q1.852 ÷ (C1.852 × d4.8704), in metres of water. 1 m of head is 0.098 bar.
C describes the pipe’s roughness: higher is smoother. The formula is empirical, for water around 5 to 25 °C; for other fluids and very small pipes use Darcy–Weisbach.
In Hermetry Hermetry watches district inflow and the pressure at critical points in a water network: Pressure and night flow watch.
Glossary Flow meter, DMA (district metered area)
Questions
Questions about the pipe head loss calculator
What velocity is usual in water mains?
Design velocities of roughly 0.5 to 2 m/s are common: lower gives stale water and settling, higher gives large losses and surge risk.
Why does diameter matter so much?
Head loss falls with the diameter to the power 4.87: a pipe one size up loses far less at the same flow.