Interrupt version is on the station since Monday. Hand tally 52, Hermetry 52 on Tuesday’s shift. I’d also been publishing “rejects this minute” and resetting to zero, so two lost messages last week had silently eaten rejects; it’s rejects.total now with the counter in RTC memory. Thanks for the Forge note Keisha. Our manager had asked me to “check Forge”, I’ll pass that to our account contact, but the counter does the job today either way.

♥ 0

Measured 9 V AC between the two building grounds, so that’s it. Isolated module ordered, shield now only at the gateway end. The disconnect after missed polls is in the script already, the offline alarm caught a meter we unplugged on purpose 15 minutes later.

♥ 0

It was both. getty was sitting on serial0, and the mini UART with even parity never worked. After disable-bt and the console off, the PM5110 answered on the first try: 230.4 V L1-N. Publishing every 10 s now. Thanks David, and Megan for pointing at Bluetooth.

♥ 1

Welcome Liam. Get one ESP32 sending one value reliably before you wire up the rest, it saves a lot of confusion later. And no question is too basic here.