Zonen mit einem Titel pro Abschnitt sind eine gute Idee. Wir machen das Gleiche für unsere Abfüllanlage.
Zones with a title per section is a good idea. Doing the same for our filling line.
Von English mit KI übersetzt ·
Wer darf hier was senden? Unsere Bediener sind alle Users.
Who can send what here? Our operators are all Users.
Von English mit KI übersetzt ·
Hallo Serhat. Ich komme hier aus der Automobilbranche. Gibt es in der Bibliothek etwas für Montagelinien, oder geht es hauptsächlich um Tanks und Pumpen?
Hello Serhat. Automotive here. Is there anything in the library for assembly lines, or is it mostly tanks and pumps?
MAX6675 tops out at 1024 °C by design, that’s your 1023.75.
Interrupt version is on the station since Monday. Hand tally 52, Hermetry 52 on Tuesday’s shift. I’d also been publishing „rejects this minute“ and resetting to zero, so two lost messages last week had silently eaten rejects; it’s rejects.total now with the counter in RTC memory. Thanks for the Forge note Keisha. Our manager had asked me to „check Forge“, I’ll pass that to our account contact, but the counter does the job today either way.
Measured 9 V AC between the two building grounds, so that’s it. Isolated module ordered, shield now only at the gateway end. The disconnect after missed polls is in the script already, the offline alarm caught a meter we unplugged on purpose 15 minutes later.
It was both. getty was sitting on serial0, and the mini UART with even parity never worked. After disable-bt and the console off, the PM5110 answered on the first try: 230.4 V L1-N. Publishing every 10 s now. Thanks David, and Megan for pointing at Bluetooth.
Baud matches. Bluetooth I haven’t touched.
Welcome Liam. Get one ESP32 sending one value reliably before you wire up the rest, it saves a lot of confusion later. And no question is too basic here.