Chiller efficiency converter: COP, EER and kW/ton

Free chiller efficiency converter: convert chiller and heat pump efficiency between COP, EER and kW per ton; enter any one and get the other two.

This chiller efficiency converter uses EER = COP × 3.412 and kW/ton = 3.517 ÷ COP: a chiller with a COP of 5 has an EER of 17.06 and uses 0.703 kW per ton of cooling.

COP
–
EER
–
kW/ton
–

Higher COP and EER are better; lower kW/ton is better.

How it works

How do you convert COP to EER and kW/ton?

COP is cooling (or heating) output divided by electrical input, both in kW. EER is the same ratio in BTU/h per watt: EER = COP × 3.412.

kW/ton is the electrical input per refrigeration ton of cooling (12,000 BTU/h, 3.517 kW): kW/ton = 3.517 ÷ COP.

A rating only holds at its test conditions; seasonal figures such as SEER average over a year’s part loads and are not directly comparable.

In Hermetry Hermetry reads chillers, boilers, air handling units and meters across a building portfolio: Building HVAC and energy overview.

Glossary Chiller, COP (coefficient of performance), HVAC (heating, ventilation and air conditioning)

Questions

Questions about the chiller efficiency converter

What is 0.6 kW/ton as a COP?

About 5.86. kW/ton = 3.517 ÷ COP, so COP = 3.517 ÷ 0.6.

Is EER the same as SEER?

No. EER is measured at one set of conditions; SEER averages over a cooling season’s part loads and conditions, so it is usually higher.