I did exactly this for a uni lab last term and got the same ERROR on BIND. The address comes out of AT+ADDR? with colons, but AT+BIND wants commas, in the order NAP,UAP,LAP:

AT+BIND=98d3,31,fb1234

Full sequence that worked for us, both modules entered with KEY/EN held high at power-up (AT mode is 38400 baud):

slave A:  AT+ORGL
          AT+ROLE=0
          AT+PSWD="4321"
          AT+UART=9600,0,0

master B: AT+ORGL
          AT+ROLE=1
          AT+CMODE=0
          AT+PSWD="4321"
          AT+BIND=98d3,31,fb1234
          AT+UART=9600,0,0

Same PSWD on both, then power-cycle both without KEY held. Master pairs within a few seconds. After that it’s a plain 9600 serial line between the Unos.

Accepted solution♥ 3

We pulled a 2-pair cable last week, used the second pair for 0 V, moved the shield from GND to the earth bar with a clamp, and put a 10 nF to earth at the far end. CRC errors went from ~3 % to 0.02 % over 4 days, and nothing changes when the fans start. The before/after chart is in my report now. Thank you.