4-20 mA scaling: from loop current to a value on the process screen

One straight line turns milliamps into bar or metres. The formula, a worked table, what a current under 4 mA tells you, and how many devices a loop can carry.

4-20 mA scaling turns loop current into an engineering value with one straight line: value = low + (current – 4) / 16 x (high – low). 4 mA is the bottom of the transmitter’s range and 20 mA the top. A current well below 4 mA means a fault in the loop or the transmitter.

Why does 4-20 mA start at 4 mA?

The 4 mA live zero lets you tell the bottom of the range from a dead loop. If the range started at 0 mA, a cut cable and an empty tank would both read 0, whichever tank level sensor you use.

A two-wire transmitter also takes its own supply from the loop current, so it needs some current even when the process sits at the bottom of its range; the 4 mA floor gives it that.

How do you convert 4-20 mA to engineering units?

Map 4 mA to the lower range value, 20 mA to the upper range value, and draw a straight line between them.

  1. Read the lower and upper range values from the transmitter’s configuration or nameplate; the tag on the P&ID names the instrument only.
  2. Convert the input channel’s raw counts to milliamps, using the counts the input card’s manual gives for 4 and 20 mA.
  3. Apply value = low + (mA – 4) / 16 x (high – low).
  4. Decide which currents count as a fault before the value reaches the screen.

For a transmitter ranged 0 to 10 bar:

Loop currentValue
4 mA0 bar
8 mA2.5 bar
12 mA5 bar
16 mA7.5 bar
20 mA10 bar

I keep the conversion in one place, close to the data, rather than repeating it on every screen.

Hermetry connects field devices to live dashboards, rules and alerts: IoT telemetry and SCADA in one platform. In its flows, a Scale block before Save telemetry maps a 4–20 mA signal to 0–10 bar with in_min 4, in_max 20, out_min 0 and out_max 10 (see derived values). If alarm rules should use the scaled value, the block goes before the Alarm rules block, on telemetry messages only. A symbol on a process drawing can also convert a raw value in a one-line binding expression.

What does a reading below 4 mA mean?

A small dip can be the process going past the calibrated range, but a reading well below 4 mA means a fault: a broken wire, lost loop power or a failed transmitter.

A digital transmitter can also report its own fault through the loop current. NAMUR’s recommendation NE 43 aims to standardise that failure signal level; the failure currents a given device uses are in its manual. On the screen, show a dimmed value with a fault mark, never 0 bar or a level of -0.3 m, because a zero makes a dead loop look like an empty tank, the same trap as a frozen reading that looks live (see whether a dashboard value is live).

How do you wire several 4-20 mA sensors?

Give each two-wire transmitter its own loop, with one twisted pair back to its own input channel. Several receivers can share one loop in series, as long as the supply covers every voltage drop in it.

The budget is Ohm’s law. Say the transmitter needs 12 V at its terminals. A 24 V supply leaves 12 V for the rest of the loop, which at 20 mA is 600 ohms. A 250 ohm input and a 250 ohm panel display fit, with 100 ohms left for cable; a third 250 ohm device does not. When the budget runs out, the loop works fine at low readings and fails near the top of the range.

Frequently asked questions

What is a 250 ohm resistor for in a 4-20 mA loop?

It turns the current into a voltage for an input that measures volts. By Ohm’s law, 4 mA through 250 ohms gives 1 V and 20 mA gives 5 V, so a 1-5 V input reads the loop. At 20 mA it takes 5 V of the loop’s budget.

Can I use 0-20 mA instead of 4-20 mA?

Some devices offer 0-20 mA, but then 0 mA means both the bottom of the range and a broken wire. I would use it only where the device cannot do 4-20 mA, and then watch the loop some other way.

Why does my scaled value show slightly negative numbers?

The current sits a little under 4 mA, for example from an offset in the transmitter or the input card, or a process just under its range. Measure the current at the input. Recalibrate a real offset, and flag a fault level as a fault instead of clamping it to zero.