Hazardous area classification: zones, divisions and what they mean for monitoring equipment

Zones, divisions, ATEX categories and IECEx certificates, read from the legal texts, and why I keep gateways outside the classified area.

Hazardous area classification divides a site by how often an explosive atmosphere can be present. The zone system grades gas areas as Zone 0, 1 or 2 and dust areas as Zone 20, 21 or 22; the North American division system uses Division 1 and 2. Electrical equipment installed there has to be selected for that classification.

On oil and gas sites and in mining, a monitoring project meets area classification as soon as a sensor or gateway has to go near the process. The classification is the site’s decision: in the EU the employer classifies places into zones under Directive 1999/92/EC, and in the US, OSHA requires zone-system locations, and division-system locations established after 13 August 2007, to be documented. Monitoring works inside that drawing.

What is the difference between zone and division hazardous areas?

Both systems grade a place by how likely an ignitable gas or vapour is; zones use three grades and divisions use two. US rules define both systems for gas: Class I, Division 1 and 2, and Class I, Zone 0, 1 and 2.

Gas, vapour or mist presentZoneClosest division by wording
Continuously, for long periods or frequentlyZone 0Division 1
Likely in normal operation occasionallyZone 1Division 1
Not likely in normal operation, and only for a short period if it occursZone 2Division 2

Division 1 covers places where ignitable concentrations may exist under normal operating conditions, or frequently because of repair, maintenance or leakage, so it spans Zone 0 and Zone 1. Division 2 covers places where the gas is normally confined in closed systems and escapes only through rupture, breakdown or abnormal operation. Dust has its own grades: Zone 20, 21 and 22 in the EU, and Class II locations in the US.

What does ATEX or IECEx certified mean for a sensor?

An ATEX marking means the manufacturer declares that the device meets Directive 2014/34/EU for the equipment group and category on the marking; IECEx means it holds an IECEx Certificate of Conformity. The category is what links a device to a zone.

  • Category 1 equipment for Zone 0 or Zone 20.
  • Category 1 or 2 for Zone 1 or Zone 21.
  • Category 1, 2 or 3 for Zone 2 or Zone 22.

These are the defaults of Directive 1999/92/EC, unless the site’s explosion protection document says otherwise. The marking adds the letter G for gas or D for dust. Category 1 and 2 electrical equipment needs a notified body’s EU-type examination; category 3 can rest on the manufacturer’s own production control, so an ATEX mark on a Zone 2 device may be a self-declaration. Every IECEx certificate is public on the IECEx website, and it is valid while its status reads “Current”. A manufacturer that changes a certified design has to tell the certification body that issued the certificate, so I would not assume a certified enclosure stays covered once a board that was not part of that design goes inside it.

Can you install a gateway in a hazardous area?

You can, if the gateway is certified for that zone or division. I prefer to keep gateways, radios and their power supplies outside the classified area, and to bring only field signals in.

US rules allow equipment approved as intrinsically safe in any hazardous location it is approved for. An intrinsically safe sensor wired through a barrier to a gateway in the safe area keeps the cabinet full of ordinary electronics out of the zone. Equipment outside can still be covered: Directive 1999/92/EC applies its minimum requirements also to equipment in non-hazardous places that is required for, or helps to ensure, the safe operation of equipment in hazardous places. Once the gateway sits in the safe area, reading the field devices is ordinary work, from Modbus register addressing to remote site UPS monitoring.

Frequently asked questions

Who decides the hazardous area zones on a site?

In the EU, Directive 1999/92/EC makes the employer classify places where explosive atmospheres may occur into zones and keep an explosion protection document, revised when the workplace changes significantly. In the US, 29 CFR 1910.307 requires zone-system locations, and division-system locations established after 13 August 2007, to be documented for those who design, install, inspect, maintain or operate the electric equipment.

Can a remote monitoring system replace gas detection?

No. Gas detection, alarms and shutdowns that protect people are safety functions with their own design, certification and testing rules. A monitoring system can show trends, readings and alarms to operators, but it does not take over the job of a safety system, and it should not be designed or presented as one.

Is an IECEx certificate enough to sell a device in the EU?

No. The IECEx scheme’s own guidance says that what is required to sell Ex products in the EU is ATEX. An IECEx certificate and an ATEX certificate are separate documents, though test data that meets the IEC standards can be used for both. Check the ATEX marking and the EU declaration for an EU installation.