Reply To: Can my relays just subscribe to their own MQTT topic, or does Hermetry want something else for actuators?

One thing from the field: make the command set a state, never toggle. A command that times out only means no answer came back, it may have run anyway. If the supervisor presses again, fan.set on twice is harmless, fan.toggle twice turns it off.

If it isn't logged, it didn't happen.