A good HMI color scheme draws the normal process in greys and muted tones and keeps strong color for the few states that need action. The US Nuclear Regulatory Commission’s interface guidelines say to use color conservatively, with as few colors as the information needs, and to use brighter, more saturated colors for critical data.
I design boards for manufacturing lines and food plants, and the first thing I take out of most screens is color. A process drawn from a P&ID already has plenty of detail; color should only add the part that needs attention.
Why are HMI screens grey?
Grey leaves color free to mean something. NUREG-0700 Rev. 3, the human-system interface review guidelines of the US Nuclear Regulatory Commission, says casual, arbitrary use of color on every display can make it busy or cluttered, and makes it less likely that the significant color coding is read quickly and correctly.
On a grey screen, one red pump stands out. On a screen with blue pipes, green tanks and a navy background, the same red pump has to compete. So I make the normal state look boring on purpose: grey equipment, grey pipes, dark grey values.
Which colors should you use for alarms on a dashboard?
Use the most saturated colors for alarms only, give each color one meaning, and pair every color with a second cue. The same NUREG guidelines ask for brighter or more saturated colors to draw attention to critical data, each color for only one category of data, and color coding that is redundant with another display feature, so the screen still works in monochrome or for a user with color vision impairment.
This is the palette I start from:
| State | Color | Second cue |
|---|---|---|
| Normal | Greys | None needed |
| Warning | Amber | Icon and label |
| Critical alarm | Red | Different icon, label, and a pulse until someone acts |
| No recent data | Outlined grey | The word Unknown instead of the last value |
For dashboards in a browser, the web accessibility rules point the same way. WCAG 2.2 success criterion 1.4.1 says color must not be the only visual means of conveying information, and 1.4.11 asks for a contrast ratio of at least 3:1 for the graphical parts needed to understand content.
How many colors should a dashboard use?
As few as the information needs. NUREG-0700 says the number of colors used for coding should be kept to the minimum needed, and that once a color has a meaning, no other color should be used for the same purpose.
Its test for colors that are easy to tell apart yields at least 7 to 10 that can be shown at once. I stay well under that: the four states above, plus one accent for whatever the operator has selected.
Hermetry connects field devices to live dashboards, rules and alerts: IoT telemetry and SCADA in one platform. On its stat, gauge and progress cards, colour ranges take up to 20 rows of From, To, Colour and Label, and the first range the value falls in colours it, so a value can stay grey in its normal band and change only outside it. State cards add an icon and a pulse option per state, a second cue besides the colour.
For a cold room temperature board, that means one grey number most of the day and a red one with an icon when someone leaves the door open.
Frequently asked questions
Should an HMI use a dark or a light background?
Either can work if the color set is chosen for it. NUREG-0700 lists different easily distinguished colors for light and dark backgrounds, warns against pure blue text or thin lines on a dark background, and asks that color be evaluated under the room’s real lighting.
Is red and green a bad pair for running and fault?
It is a risky one. NUREG-0700 says red and green should not be used in combination whenever possible, especially red symbols on a green background. If a plant convention requires them, add a shape or label so the state reads without color.
Can I show a tank level as a color gradient?
Not for decisions. NUREG-0700 keeps gradual color changes for relative values, such as depth across an area, and says they should not show a storage tank’s level as it fills or drains; discrete codes for dangerous and acceptable levels fit better.