Switchgear vs MCC comes down to what each cabinet feeds. Switchgear switches and protects a plant’s main power feeders with circuit breakers. A motor control center (MCC) groups the starters and drives for many motors on a common bus. A distribution board splits one supply into small protected circuits for lighting, sockets and small loads.
In a typical plant the three sit in a chain: switchgear at the incoming supply, feeding MCCs and distribution boards, which feed the loads. What you can measure in each follows from that position.
What is a motor control center?
A motor control center is a set of enclosed sections that share a power bus and hold the control units for many motors. US workplace safety rules (OSHA 29 CFR 1910.399) define it as “an assembly of one or more enclosed sections having a common power bus and principally containing motor control units.”
A typical unit serves one motor, with a disconnect, short-circuit protection and a starter or a variable-frequency drive. That makes the MCC the best place to watch motors: run, stop and tripped status per unit, motor current, overload trips, run hours and the number of starts. Current against the motor’s normal value shows a change in load, such as a pump that has lost its suction or a conveyor that has jammed.
What is the difference between switchgear and a distribution board?
Switchgear handles the large feeders, and a distribution board handles final circuits. IEEE describes switchgear as equipment used for switching, interrupting, metering, protection and regulating in the generation, transmission, distribution and conversion of electric power; OSHA describes a panelboard, the US term for a distribution board, as a panel with buses and automatic overcurrent devices, placed in a cabinet and accessible only from the front.
The difference in what you can read is as large as the difference in duty. In switchgear I expect breaker position contacts, protection relays and multifunction meters on each feeder. In a distribution board I expect, at most, a meter on the incomer and a few sub-meters, with breakers that report nothing unless someone wired an auxiliary contact.
Which electrical values should you monitor in switchgear?
Monitor breaker state and trips first, then the loading and temperature of each feeder, then power quality. A trip stops whatever the feeder supplies, and loading and temperature give warning before one.
| Cabinet | Read | Alarm on |
|---|---|---|
| Switchgear | Breaker open, closed and tripped; relay trip; voltage and current per phase; power and energy per feeder; busbar or joint temperature; harmonic distortion | Any unplanned trip, a breaker that changes state without a command, temperature rising faster than load |
| MCC | Run, stop and trip per motor; motor current; drive faults; run hours; starts | Overload and drive trips, current outside the motor’s normal band, too many starts |
| Distribution board | Incomer energy; sub-meter energy per circuit; tripped breakers where contacts exist | A circuit drawing power when its area is closed |
Compare temperature with current, not with one fixed limit: a loose connection has a higher resistance and heats up more under load, so a joint that runs hotter than its neighbours at the same current needs attention. Where a meter or relay offers Modbus, read its registers instead of wiring more contacts (more on Modbus register addressing), and if a UPS backs up the board, read it as in remote site UPS monitoring.
Monitoring reports what the protection did and never replaces it: the relay and breaker clear a fault on their own, whatever the screen shows. For secondary substations, see distribution substation and transformer monitoring and the energy industry page.
Frequently asked questions
What is the difference between a switchboard and a panelboard?
In OSHA 29 CFR 1910.399, a switchboard is a large panel, frame or assembly of panels carrying switches, protective devices, buses and usually instruments, generally accessible from the rear as well as the front and not installed in cabinets. A panelboard is designed to sit in a cabinet or cutout box in or against a wall and is accessible only from the front.
Can you add monitoring to an existing distribution board?
Yes, where the cabinet has room, with split-core current transformers, which close around a conductor without disconnecting it, wired to a meter that reports energy per circuit. The work still means opening a cabinet that is normally energised, so a qualified electrician should plan and do it under the site’s electrical safety procedures.
Should an MCC report each motor or only the cabinet total?
Each motor, if you want to find problems. A cabinet total shows that load changed but not which motor changed it. Per-unit run status, current and trip signals let an operator see which pump or fan stopped and why, and run hours per motor feed maintenance planning.