Server room and critical environment monitoring

A blueprint for watching temperature, humidity, water, power, cooling and doors in server rooms and electrical rooms, with alarms that reach IT and facilities at any hour.

At a glance

ItemTypical answer
ProblemServer rooms, branch comms rooms and electrical rooms are unmanned; cooling failures, leaks and UPS problems are noticed when equipment shuts down.
What is connectedRack inlet temperatures, humidity, leak detection, doors, UPS and power distribution values, precision cooling units, generator and transfer switch states.
Who uses itIT operations, the facilities or data centre engineer, the security desk and the IT manager.
Typical first scopeThe main server room plus three to five branch rooms.
Time to first screenTypically a day for a branch room using the Remote sites solution; one to three weeks for a main room whose UPS and cooling units are read over Modbus.
Estimates; access to the UPS and cooling unit interfaces often decides the timeline.

The situation

A company with a main server room and tens of small comms rooms in branches, factories or stores relies on rooms that nobody sits in. The main room has precision cooling units, a UPS, perhaps a generator; each branch room has a rack, a split air conditioner and a small UPS. Electrical rooms with switchgear and the generator transfer switch sit next door.

The typical incidents: a split unit trips on a Friday night and the branch rack reaches 45 °C by Saturday morning; a condensate pump fails and water spreads under the raised floor; a UPS has been running on a failed battery string for months and drops the load at the first power blip; a door to the electrical room is left unlocked. IT monitoring tools see servers going down, not the room around them, and the building management system, where one exists, does not reach the branches and does not page IT.

The aim: every critical room on one screen, readings close to the equipment's air inlets, alarms that wake the right person for the right reason, and a record that shows what happened before an outage.

Goals and measures

  • Inlet compliance = time each rack inlet sensor is within the agreed band ÷ time in the period. A commonly used recommended inlet band is 18 to 27 °C; agree yours with the equipment owners.
  • Hottest inlet per room per day from day aggregates, to find hot spots and blanking problems.
  • Power usage effectiveness = total facility energy ÷ IT energy, per day, from the increase of the facility meter and the UPS output meter, where both exist.
  • UPS runtime margin = minutes of runtime remaining at the current load, and the last self-test result per UPS.
  • Cooling redundancy = number of cooling units running and healthy against the number needed for the load.
  • Time to acknowledge for Critical alarms, measured from the alarm timeline, in and out of working hours.

Architecture

Server rooms are on corporate networks that rarely allow inbound connections, and their UPSs and cooling units usually sit on a private management network. The design therefore reads everything on site and sends it out over one outbound connection.

  • Main room: a licensed gateway running Hermetry Edge on the management network reads the UPS and precision cooling units over Modbus TCP or Modbus RTU through their interface cards, Modbus temperature and humidity sensors on an RS485 line along the racks, and dry contacts on its digital inputs: leak detection controller, door contacts, generator running, transfer switch position and the fire panel's auxiliary fault output. It sends everything over MQTT with TLS on port 8883.
  • Branch rooms: a smaller licensed gateway or a licensed 4G router with your own SIM, reading a temperature and humidity sensor, a leak sensor, a door contact and the UPS. Where cabling is hard, LoRaWAN sensors with a LoRaWAN gateway do the same job.
  • SNMP: Hermetry's cloud poller can read UPS-MIB, HOST-RESOURCES and interface data over SNMP v2c or v3, but only from a host at a public address with the poller's fixed source addresses allowed. Most UPS cards in server rooms are private, so the gateway path above is the normal one. SNMP polling by the gateway on site is in development.
  • Cameras: RTSP cameras and recorders can show live views next to the room data, if the platform can reach them; recording stays in your video system.
ComponentRoleNotes
Licensed gateway with EdgeReads Modbus devices and contacts, publishes telemetryOn the management network; outbound only. Factory identity, claimed into the organisation.
Rack inlet temperature sensorsAir the IT equipment breathesFront of rack at bottom, middle and top in critical racks; Modbus RTU or LoRaWAN.
Room temperature and humidity sensorRoom air and dew pointOne or two per room, away from supply air outlets.
Leak detectionWater under raised floor, near cooling units and pipesLeak rope with a controller contact, or LoRaWAN spot sensors.
UPS interface cardUPS values over Modbus TCP or RTURead-only. SNMP only if the card has a reachable public address.
Precision cooling interfaceUnit states, temperatures, alarmsModbus RTU or TCP card of the unit.
Energy metersFacility and IT energyModbus RTU; needed for power usage effectiveness.
Licensed 4G routerUplink for branches without a usable line, and a backup patheSIM management from the platform is in development (Hermetry Connect).

Licensed devices authenticate with X.509 certificates from the platform's own authority; the profile requires TLS and can restrict source networks to your egress addresses. The gateway reports the UPS, each cooling unit, the sensor line and the meters as child devices, so each appears with its own readings, alarm rules and history.

Point list

A main room with two cooling units and one UPS. Register numbers are placeholders; take them from each card's Modbus map. Keys for UPS values follow the names of the platform's SNMP UPS template, so boards look the same whichever path a UPS uses; over Modbus, status values such as the output source arrive as the card's numeric codes, so write rules against those codes.

PointTelemetry keyUnitSourceIntervalNotes
Rack inlet temperature, per positioninlet_r01_top_c, inlet_r01_mid_c, …°CModbus RTU sensor, input register 3000160 sOne key per sensor position; or one child device per rack.
Room temperatureroom_temp_c°CRoom sensor60 s
Room humidityroom_rh_pct%Room sensor60 s
Room dew pointroom_dewpoint_c°CRoom sensor, if it reports it60 s
Water leakleakboolLeak controller contact, DI1on changePlus a heartbeat every 5 min.
Leak zoneleak_zonenumberLeak controller Modbus, if availableon changeWhich section of rope is wet.
Door opendoor_openboolDoor contact, DI2on change
Fire panel fault or pre-alarmfire_auxboolFire panel auxiliary output, DI3on changeInformation only.
UPS output sourceoutput.sourcetextUPS card30 snormal, bypass, battery and others.
UPS battery chargebattery.charge%UPS card60 s
UPS runtime remainingbattery.minutes_remainingminUPS card60 s
UPS battery temperaturebattery.temperature°CUPS card5 minBattery life halves with heat.
UPS output load, phase 1-3output.load.1, output.load.2, output.load.3%UPS card60 s
UPS input voltage, phase 1-3input.voltage.1, …VUPS card60 s
UPS alarms presentalarms.presentcountUPS card60 s
UPS last self-testtest.resulttextUPS card1 h
Cooling unit runningcu1_run, cu2_runboolCooling unit card60 s
Cooling unit return air temperaturecu1_return_c°CCooling unit card60 s
Cooling unit supply air temperaturecu1_supply_c°CCooling unit card60 s
Cooling unit alarmcu1_alarmcodeCooling unit card60 sMap codes in the runbook.
Generator runninggen_runboolGenerator contact, DI4on change
Transfer switch on generatorats_on_genboolATS contact, DI5on change
Facility energyfacility_kwhkWhMain meter15 min
IT energyit_kwhkWhUPS output meter15 min
About 40 keys for a main room, 8 to 12 for a branch room.

Asset model

  • Site per building or branch, with address, location, time zone, site_code, it_contact and facilities_contact.
  • Room per server room, comms room or electrical room, with room_type, tier (critical, important, standard), design_kw and inlet_band.
  • Machine per UPS, cooling unit and generator, with model, rated_kva or rated_kw, battery_installed and service_contract.
  • Other (free kind Rack) for each critical rack, with rack_id and owner_team.

Place each child device on the asset it measures. Add Feeds relations from the UPS to the room and from the transfer switch to the UPS, so a site page can show what depends on what, and Monitors relations from inlet sensors to their racks. Status rolls up: a rack in alarm turns its room and site amber or red on the overview.

Limits that vary by room go on the devices as server attributes, for example inlet_high_c = 27 for a standard room and 25 for a room with older equipment. Rules compare with the attribute; a device that lacks it is not checked for that limit, so include the attributes in commissioning.

Device setup

Start from the Remote sites solution

Branch rooms map well onto the Remote sites solution. It installs a site controller profile with temperature, humidity, door, water leak and smoke keys and sensor batteries, a UPS profile, threshold rules on per-site attributes, offline rules and a UPS watchdog flow that raises a warning when a UPS unit falls silent, plus a board with Sites, Alarms, Site, History, UPS and Camera pages. Adapt its keys to your sensors or map your sensors to its keys. Use separate profiles for the main room: Main room sensor line, UPS (Modbus), Cooling unit, Power and generator.

Provisioning

Claim each licensed gateway by scanning its code and place it on its room. Child devices are created when the gateway first reports them, with the profile taken from the type the gateway sends; place each on its asset. The Recent message online rule with an expected interval of one to two minutes plus an inactivity alarm per profile catches a gateway or child that goes quiet.

Settings and polling

Remote device settings show the gateway model's Modbus addresses, serial parameters and polling intervals. Configure one branch, save a baseline and apply it to all branches with a bulk job in waves; a dry run shows the differences first, and the job stops itself if too few gateways take the change. Poll the UPS output source every 30 seconds so a transfer to battery is seen quickly; inlet temperatures every minute. If the gateway model supports report by exception, use a deadband of about 0.3 °C on temperatures with a heartbeat.

Time and continuity

Synchronise the gateway's clock with your internal time servers; readings more than ten minutes ahead are dropped. When the uplink fails, licensed gateways buffer readings and send them later, within a capacity that depends on the model. Alarm rules evaluate late readings as a backfill: the history shows what happened during the outage, marked Backfilled, and nobody is paged for the past. A branch whose only uplink is the corporate network goes silent exactly when that network fails; a licensed 4G router as a second path avoids that blind spot.

Firmware

Signed gateway firmware rolls out from the profile in waves with soak times; a failed wave pauses the rollout. Devices on 4G wait for metered downloads unless allowed. Begin with the least critical branch.

Dashboards

BoardAudienceWidgets and what they show
Rooms overviewIT operations, security deskMap of sites coloured by alarm state; table of rooms with hottest inlet, humidity, door, leak, UPS source and last reading; stat cards for open Critical alarms, rooms on battery and devices offline; alarm table. Shown on the operations wall screen through a read-only display link.
Room pageIT and facilities engineersInlet temperatures per rack as a heatmap or table; gauges for room temperature and humidity; state cards for door, leak, cooling units and UPS source; line chart of inlets and cooling return and supply over 24 hours; the room drawing; the room's alarms.
UPSFacilitiesBattery charge and runtime as progress cards; output load per phase; input voltages; last self-test result in words; battery temperature trend over 90 days.
Energy and capacityIT managerDaily facility and IT kWh and their ratio against the previous period; output load trend against UPS rating; cooling units running.
CamerasSecurity deskLive views of the room cameras next to the door state, if cameras are connected.

Entity parameters keep one room page for all rooms; the overview opens it by drill-down with the room as a parameter. The UPS page takes the UPS device that feeds the chosen room.

SCADA screens

  • Room layout: a plan of the room with rows of equipment racks, the precision cooling units and the UPS, from the telecom family; inlet temperatures printed on each rack and coloured by limit; the cooling units showing running, standby and alarm; the UPS showing normal, bypass and battery from output.source.
  • Power path: a single-line drawing from the Power pack with busbar, circuit breaker and switchgear cabinet symbols, the standby generator and transfer switch from the Building pack, and the UPS; the active path highlighted by rules on ats_on_gen and output.source.
  • Network corner: network switch, firewall and gateway router symbols from the telecom family where a drawing of the comms rack helps the branch technician.
  • Reuse: draw a branch room once, attach it as a view of every branch site and let Match everything bind each site's devices. A 3D view made from the room plan keeps its bindings and helps on-site staff find a rack.

See the SCADA library for the packs. Clear the designer's Problems tab before publishing.

Rules and alarms

AlarmConditionDelay and hysteresisSeverityNotifiedEscalation
Rack inlet highany of up to 16 inlet keys > attribute inlet_high_c (Major); > attribute inlet_crit_c (Critical)Debounce 3 samples; hysteresis 1 °CMajor / CriticalIT operations, push and chat; Critical also SMS to the duty engineerRise to Critical notifies again; reminder every 15 min
Room humidity out of bandroom_rh_pct > attribute rh_high or < attribute rh_lowDebounce 10 min; hysteresis 3 %MinorFacilities, e-mailReminder every 60 min
Water leakleak == trueDebounce 1 sampleCriticalFacilities and IT duty, SMS and pushReminder every 5 min
UPS on batteryoutput.source == battery, or the UPS card's numeric code for battery when read over ModbusDebounce 2 samplesMajorFacilities and IT operations, SMSReminder every 10 min
UPS runtime lowbattery.minutes_remaining < attribute runtime_minDebounce 2 samplesCriticalIT duty and IT manager, SMSReminder every 5 min
UPS on bypassoutput.source == bypassDebounce 2 samplesMajorFacilities, e-mail and pushReminder every 30 min
UPS self-test failedtest.result == doneErrorMajorFacilities, e-mailNone
Cooling unit alarmcu1_alarm != 0Debounce 2 samplesMajorFacilities, pushReminder every 30 min
Both cooling units stoppedall: cu1_run == false, cu2_run == falseDebounce 60 sCriticalFacilities and IT duty, SMSReminder every 5 min
Door open out of hoursRules card: door_open becomes true outside the access windowMinorSecurity desk, push and in-appNone
Room device silentInactivity rule, 5 minMajorIT operations, pushReminder every 30 min

Rate of rise. A cooling failure shows as a fast climb long before any threshold. Alarm rules compare values, not slopes; a flow in the room profile's root can compute the change between readings with a delta block and store it as inlet_rise_c with a save block. An alarm on inlet_rise_c > 2 between one-minute readings then warns minutes earlier than the threshold.

Power events without a flood. A mains failure puts every UPS on battery and may start the generator. Keep UPS on battery at Major and let UPS runtime low carry the Critical, so the night page comes only when time is short. The transfer switch and generator states explain the event on the drawing. If more than 20 alarm notifications a minute would go out, Hermetry collects the rest into a five-minute digest.

Lifecycle and records. Alarms open after their debounce and clear themselves. The duty engineer acknowledges and adds notes on the timeline, for example the split unit reset and the ticket number; acknowledgements and clearances are audited under the person's name. Each rule carries a runbook: which breaker, which contractor, which shutdown order. Escalation follows severity: a rise from Major to Critical notifies again, and reminders repeat until someone acknowledges. Hermetry has no on-call rotation for IoT alarms, and alarm rules notify users, roles or e-mail addresses, not groups; route alarms to a shared duty address, or add a Rules-card rule on the alarm that notifies a duty team whose members you change each week.

Maintenance. Mute a room's devices during UPS battery replacement or cooling service. Alarms still record, marked as muted; a mute ends by itself, after at most 90 days.

Automation and integrations

  • Ticketing: the signed webhooks alarm.created, alarm.acknowledged and alarm.cleared create and update tickets in the IT service management tool; a flow can instead post only Major and Critical alarms through an HTTP request.
  • Chat: alarm notifications can go to Telegram, Slack, Discord or WhatsApp where your organisation has connected them, next to SMS, push, e-mail and in-app.
  • Local outputs: a licensed gateway with relay outputs can drive a siren or start an extract fan through a command from its catalog, if the model and firmware support the method; a Rules card rule can send it when the room stays above 35 °C for 5 minutes. High-impact commands need a typed confirmation and are audited. The UPS, cooling units and generator keep their own controls; no commands go to them.
  • Remote work on routers: an engineer can open the web panel of a licensed router from its device page through router remote access, in sessions limited in time and audited, without a fixed IP or VPN.
  • Reports: history tables download to Excel for monthly capacity and energy reviews. Scheduled or e-mailed reports are not built in today.

Roles and access

WhoRole or groupCan
IT operationsUser + IoT operator groupSee all rooms, acknowledge alarms, send basic commands, write limit attributes.
Security deskUserSee door, leak and camera views; acknowledge door alarms.
Facilities engineerUser + IoT operator groupSee power and cooling devices, acknowledge, add notes.
Branch IT contactUser, narrowed by a policy to their siteSee their room only.
IT managerUser + IoT viewer groupRead everything, export history.
Platform administratorAdminProfiles, rules, boards, command catalog, mutes, firmware.

Attribute-based policies narrow a member to single devices or the devices of one site. Sign-in can go through your SAML or OIDC identity provider with two-factor authentication or passkeys, which suits an IT department. The AI firewall watches sign-ins, API calls and device traffic, blocks abuse and explains each decision. The audit log records sign-ins, role changes, commands, acknowledgements and setting changes in a hash chain that Verify checks, exportable as CSV or NDJSON.

Sizing and data

As an order of magnitude for one main room and 30 branch rooms:

  • Main room: about 8 child devices sending once a minute, and the UPS source every 30 seconds: roughly 8 × 1,440 + 2,880 = 14,400 messages a day.
  • Branch rooms: one gateway with two children (sensors and UPS) at one message a minute each, 30 × 2 × 1,440 = 86,400 messages a day.
  • Contacts and heartbeats: allow 100 per room a day, 3,100.
  • Total: about 104,000 messages a day, roughly 3.1 million a month. Alarms, commands and connection events do not count against the allowance.
  • If the branches report every 5 minutes instead of every minute, the total falls to about 35,000 a day; inlet temperatures in a small room rarely need more.

The plan's retention class, from 7 to 1,095 days, sets history length: raw readings are kept for at most 90 days, minute aggregates for up to 31 days, and hourly and daily aggregates for the full class, which make year-on-year capacity charts cheap. The 365-day class, with 90 days of raw data and a year of aggregates, is a common choice for server rooms. Each device's default limits of 10 messages a second and 300 a minute leave plenty of headroom.

Rollout plan

PhaseWeeksWorkExit criteria
0. Survey1-2List rooms, UPS and cooling models with their interface cards and Modbus maps; network path for outbound MQTT; alarm limits and duty team agreed.Point list per room type; firewall rule for outbound 8883 approved.
1. Main room3-5Gateway, sensor line, UPS and cooling cards; profiles, alarm rules, room drawing, webhooks to ticketing.Values match the UPS and cooling displays; every alarm forced and handled end to end.
2. Branch pilot6-7Remote sites solution adapted; three to five branches; baseline for branch gateways.Two weeks without unexplained gaps; nuisance alarms under one per room a week.
3. All branches8-16Remaining branches in batches; 4G backup paths where needed; display link on the operations wall.All rooms online; a weekend power-failure drill passed in one branch.

Commissioning checklist

  1. Gateway claimed, certificate active, outbound connection on 8883 works through the corporate firewall.
  2. Each child device on the right profile and asset; limit attributes present.
  3. Each inlet sensor compared with a reference thermometer at the rack front; position labels match keys.
  4. Leak rope wetted at its far end: Critical alarm by SMS; clears when dry.
  5. UPS switched to battery in a planned test, or its self-test run: output.source changes, the alarm opens, runtime readings fall as expected.
  6. Cooling unit stopped in a controlled test: unit alarm, rising inlets, rate-of-rise alarm before the threshold alarm.
  7. Door opened out of hours: security desk notified.
  8. Uplink unplugged for 15 minutes: offline alarm; buffered readings and backfilled alarms after reconnection; 4G backup path tested where fitted.
  9. Ticketing webhook receives created, acknowledged and cleared events with valid signatures.

Pitfalls

  • Sensors on the wall. Room air near the door says little about rack inlets. Measure at the front of the racks at several heights.
  • SNMP assumed to work from the cloud. UPS cards on private networks cannot be polled from outside; read them through the gateway.
  • Every UPS event Critical. Transfers to battery happen during every short dip. Page on runtime, not on the transfer.
  • Single uplink through the network being monitored. When the core switch fails, the room goes silent. Add a 4G path for critical rooms.
  • No limit attribute on new devices. A device without the attribute is not checked for that limit. Make attributes part of the add-device routine.
  • Duty team out of date. Notifications reach people who left. Review the team membership and alarm recipients when the duty roster changes.

What Hermetry does not replace

Hermetry monitors, alerts and records. Fire detection and suppression, emergency power-off, UPS and cooling controls, generator start and transfer logic stay in their own systems and hard-wired circuits and must work without the platform. Server and network monitoring stays in your IT monitoring tools; Hermetry watches the room around them. Video recording stays in your video system.

See your field data live this week

Start a trial in your region with your first devices, or book a demo and bring your own use case.