Reply to Modbus RTU meter reads 0 after gateway restart

Translated from Türkçe by AI ·

Thanks, I increased the startup delay to 30 seconds and set the read timeout to 500 ms. The problem is solved. I also added the hold_last_value: true setting to the device profile, and the dashboards no longer drop to zero. I also updated the gateway software to version 2.4.

Plant engineer, water utilities.