Had the exact same thing in a lab last term with a fridge logger. Modbus registers are just 16 bits, they don’t know about signs. Your Arduino stores -125 as two’s complement, which is 0xFF83, and as an unsigned number that’s 65411. The Pi then reads it as unsigned.

So convert it back on the Pi:

raw = rr.registers[0]
if raw > 32767:          # top bit set means negative in int16
    raw -= 65536
temp = raw / 10           # -12.5

Or let pymodbus do it, the client has a helper for this (in 3.x):

temp = client.convert_from_registers(rr.registers, data_type=client.DATATYPE.INT16) / 10

On the Arduino side, cast before the register so rounding is explicit: holdingRegisters[0] = (uint16_t)(int16_t)lround(temp * 10);. With int16 x10 you have -3276.8 to 3276.7 C, plenty for a freezer.

If a gateway polls it instead of your script, set that register’s type to signed 16-bit in the gateway config and it does the same conversion.

Timestamps in UTC or it didn't happen.
Solution acceptée♥ 9

Traduit de English par IA ·

J’ai suivi un module sur ce sujet le semestre dernier, puis j’ai passé un été à installer des passerelles dans une laiterie, alors voici ma réponse.Le maillage fonctionne à la maison parce que les routeurs sont alimentés sur secteur et écoutent en permanence. Les équipements finaux LoRaWAN sont des capteurs sur batterie qui dorment presque tout le temps et n’ouvrent de courtes fenêtres de réception qu’après l’envoi d’un message. Un nœud endormi ne peut pas relayer le trafic des autres, donc le réseau est une étoile d’étoiles : chaque passerelle à portée entend chaque uplink, et le serveur réseau élimine les doublons. Plus il y a de passerelles, plus la couverture est large, et sur Hermetry, un message d’équipement n’est stocké qu’une seule fois, quel que soit le nombre de passerelles qui l’ont reçu.James, le statut Pending est bien réel : il concerne les passerelles relais vues mais pas encore acceptées. Un relais reste toutefois un boîtier de plus à installer et à alimenter, et pour quatre capteurs derrière un même entrepôt, une seconde passerelle est plus simple.Vos deux équipements détectés se connectent en SF12 avec un SNR d’environ -15, ce qui est à la limite. La requête de join passe, mais la réponse de join doit revenir à l’équipement 5 s plus tard en RX1, ou 6 s plus tard en RX2 à 869,525 MHz (DR0), et avec cette marge, le downlink n’arrive souvent pas. Les deux autres n’atteignent probablement jamais la passerelle.Placez une seconde passerelle directement dans l’entrepôt, idéalement du côté faisant face à ces capteurs. Il peut s’agir d’une autre passerelle Basics Station ou d’un routeur sous licence équipé d’une radio LoRa. Les deux s’enregistrent auprès du même serveur réseau, et les capteurs utilisent simplement celle qui les entend le mieux.Relais et autres moyens d’étendre la couverture : Mode local et relais

Timestamps in UTC or it didn't happen.
Solution acceptée♥ 4

Traduit de English par IA ·

La source d’exemple tombe à point nommé pour moi. Mes capteurs pour mon projet de fin d’études arrivent dans deux semaines et je dois faire une démonstration de la carte avant cela. Y a-t-il des points à surveiller si je laisse les cartes d’exemple dessus ?

Timestamps in UTC or it didn't happen.
♥ 0

Both of them are partly right. U.FL is Hirose’s name. IPEX makes a family called MHF, and the original MHF (sometimes MHF1 or MHF I) mates with U.FL, so those pigtails are interchangeable. MHF4 is a smaller connector (about the size of a W.FL) and does not mate with U.FL at all, which is what Aisha hit. Newer LTE modules use MHF4 a lot to save space, sometimes only on the main antenna.

So check the mechanical drawing of the modem, not the word « IPEX ». Height around 2.5 mm is MHF1/U.FL, around 1.2 mm is MHF4.

Two other things. These connectors are rated for only about 30 mating cycles, so don’t plug and unplug them for every test. And keep pigtails short: the thin 1.13 mm cable loses a fair bit at LTE frequencies, a 30 cm pigtail where 10 cm would do costs you signal.

Timestamps in UTC or it didn't happen.
Solution acceptée♥ 1

Built it with load cells (two per bed, HX711, ESP32) and the Rules card. Test last night with my supervisor lying on a spare bed and getting up at 23:10: the alarm opened at 23:20 and the carer got it in the chat app.

One thing I got wrong first: I left my old alarm rule on the profile switched on, so the 3 p.m. lounge alarms kept coming. Deleted it, only the Rules card is left. And Rachel, the manager is getting written consent from the families before we put the other two in.

Timestamps in UTC or it didn't happen.
♥ 0

Traduit de English par IA ·

Les sondes sont-elles câblées sur 3 fils ou en alimentation parasite ? Et quand vous dites pattes courtes, c’est combien court ?

Timestamps in UTC or it didn't happen.
♥ 2

Traduit de English par IA ·

TIL : la limite est de 10. Notre laboratoire compte 12 Raspberry Pi qui font tourner un navigateur kiosque, tous connectés avec le même compte, et ils n’arrêtent pas de se déconnecter mutuellement. Maintenant je comprends pourquoi lol

Timestamps in UTC or it didn't happen.
♥ 0

Traduit de English par IA ·

Juste, une alarme par livreur aurait été absurde. Je pique le circuit optocoupleur pour la porte de notre labo.

Timestamps in UTC or it didn't happen.
♥ 0

Traduit de English par IA ·

Question d’un étudiant : pourquoi le PRV est-il placé après la branche du réservoir et non juste après la station de pompage ?

Timestamps in UTC or it didn't happen.
♥ 0

Traduit de English par IA ·

Règle d’alarme sur le profil avec ring == 1 ? C’est ce que nous avons fait pour les alertes de notre réfrigérateur de laboratoire.

Timestamps in UTC or it didn't happen.
♥ 0

We did this in our control systems module last term and I’ve since drawn a few panels for a summer job, so here’s the IEC way as we were taught it.

Designation: IEC 81346 letter codes, terminal strips are X. First strip -X1, second -X2. A single terminal is the strip plus its number with a colon: -X1:3. Equipment gets its own code too: power supply -T1, fuses -F1, the gateway maybe -A1.

Symbol: IEC 60617 draws a terminal as a small circle (or a small square, many CAD libraries use that for terminal blocks) with the number next to it, on the wire where it passes through the strip. You don’t draw the whole strip as one box in the circuit diagram, each terminal appears where its wire is.

Then a separate terminal diagram (terminal plan) per strip: a table, one row per terminal, with internal destination on one side (e.g. -A1:A+) and external cable/core on the other (W12 core 1). Electricians wiring on site work almost only from that list.

A few habits that made my drawings get fewer questions:

  • Keep field power and signals on separate strips like you do, and say so in the strip’s title (X1 24 V field, X2 RS485 + 4-20 mA).
  • Draw jumpers between terminals explicitly.
  • For the RS485 terminals, mark A/B and the shield terminal clearly and note where the 120 Ω termination sits.
Timestamps in UTC or it didn't happen.
Solution acceptée♥ 2