Reply To: Tapping a 4-20 mA loop that already feeds a locked PLC without disturbing it

Went with a loop-powered splitter, the budget worked out with 4 V to spare. The node reads the second output, Scale block gives level_pct, and I kept the raw mA key with an alarm below 3.8. The PLC reading didn’t move when we cut the node’s power to test.