Sensors on campus lamp posts with no wiring, can we power them wirelessly?

Sensors on campus lamp posts with no wiring, can we power them wirelessly?

Çözüldü 6 6

Facility manager at a hotel campus, pretty new to IoT. We are in the US, if that matters. We have 40 path lights between the buildings, a few waste bins and some planters. The owner saw a video about wireless electricity and asked me if we can put sensors on the posts (light status, bin fill, soil moisture) without digging up the paths to run cables.

I see there’s a Hermetry City section here. Is that what we’d use? And is wireless power a real option or did the owner see a demo that doesn’t scale? I don’t want to buy the wrong thing.

♥ 1

Following, our buildings want the same for the parking lot lights.

Timestamps in UTC or it didn't happen.
♥ 1

Wireless power works over centimetres (phone chargers). Over metres you get microwatts and terrible efficiency. Your owner saw a demo.

Measure twice, poll once.
♥ 0

For the water network we use battery loggers that last years on a few readings a day. That is what “no wires” looks like in practice.

QoS 1 and a lot of patience.
♥ 0

OK so batteries. Does Hermetry City handle that or do I need something else?

♥ 0

Do this kind of work for a council, so a few things.

Whatever Hermetry City adds, I found no doc page for it, so I can’t tell you. Everything you described works with ordinary devices, profiles, alarms and a dashboard.

Power: the path lights already have power at the top of the post. Lots of posts have a photocell socket, and sensor nodes made for those sockets take their power from it. That covers light status and anything mounted on the post. Bins and planters: battery sensors, reading a few times a day.

Radio: LoRaWAN suits bins and planters. The network server uses your gateway’s frequency plan, so in the US get a 915 MHz gateway and sensors on the same plan, see Regions and frequency plans. Where the hotel’s Wi-Fi reaches, Wi-Fi sensors are fine too. Battery Wi-Fi sensors should wake, send over HTTPS and sleep, give them a profile with the Recent message online rule.

Then a threshold rule on battery and a Device offline rule on each profile, so you hear about a dead sensor before a guest complains about the bin.

Kabul edilen çözüm♥ 7

Put hysteresis on the battery rule, something like below 20 with a margin of 5. Cold mornings make batteries dip and you’ll get an alarm every dawn otherwise.

♥ 2
7 yazı görüntüleniyor – 1 ile 7 arası (toplam 7)