Yeni: Yapay zekâ güvenlik duvarı tüm platformu izliyor ve her olayı sade bir dille açıklıyor. Nasıl çalıştığını görün

Reply To: MAX485 on our gateway dies every few weeks on an 80 m bus between two buildings

Measured 9 V AC between the two building grounds, so that’s it. Isolated module ordered, shield now only at the gateway end. The disconnect after missed polls is in the script already, the offline alarm caught a meter we unplugged on purpose 15 minutes later.

♥ 0