Reply To: Paper towel level alarms fire every time someone pulls a towel

I’m new to IoT too, but we did exactly this for soap dispensers in our buildings last year and fought the same e-mail flood, so here’s what ended up working.

Send a fill level in percent instead of millimetres, it’s easier for the cleaners to understand: fill_pct = (190 - dist) / 150 * 100 on the ESP32. Then add debounce and hysteresis to the rule so one odd reading can’t open it, and a reading hovering at the limit can’t close and reopen it. Ours, adjusted to your numbers:

{
  "type": "paper_low",
  "title": "{{device.name}}: paper at {{value}} %",
  "severities": [
    { "severity": "WARNING", "condition": { "key": "fill_pct", "op": "<", "value": 20 } }
  ],
  "debounce": { "mode": "count", "raise": 4, "clear": 2 },
  "hysteresis": 10,
  "notify": {
    "recipients": [ { "kind": "email", "email": "cleaning-lead@yourcompany.example" } ],
    "minSeverity": "WARNING"
  },
  "enabled": true
}

With readings every 30 s, raise 4 means it has to be low for about 2 minutes in a row, and it only clears once it’s back above 30 % (after a refill). Paste it in the profile’s Alarm rules tab in JSON mode. E-mail only goes to explicit addresses in the notify block, so use the supervisor’s address there, not a role. Name the devices after the restroom („2F Men, towels“) because the title uses the device name. The debounce settings are explained on Debounce, hysteresis and dampening.

Timestamps in UTC or it didn't happen.