Reply To: Small UPS for a remote gateway, or does Hermetry Edge buffering make it unnecessary?

That cleared up my confusion, thanks Emily. Ordered a 12 V DC UPS module with a relay output and wired it to a spare input. Next mains drop was Tuesday, 11 minutes: we got one “mains failed” alarm, no offline alarms, and no gaps in the meter charts. We’ll keep the LTE buffering question for when we replace the gateway.