Novedad: el cortafuegos de IA supervisa toda la plataforma y explica cada incidente con palabras sencillas. Vea cómo funciona

Reply To: RS-485 cable shield: earth, 0 V of the supply, or both ends?

We pulled a 2-pair cable last week, used the second pair for 0 V, moved the shield from GND to the earth bar with a clamp, and put a 10 nF to earth at the far end. CRC errors went from ~3 % to 0.02 % over 4 days, and nothing changes when the fans start. The before/after chart is in my report now. Thank you.

♥ 1