Reply To: Alarm when a contactor stays closed after the PLC output drops (welded contacts)

Went with the PLC discrepancy bit, 3 s timer, plus the local trip. Hermetry alarms on sf1.discrepancy == true for all six supply fans through one profile rule. Tested by forcing the aux input and got the alarm and the e-mail within seconds. Kept your JSON version in my notes for the sites where I can’t touch the PLC program.