Reply To: Eight meters on 30 m of RS-485 at 9600 baud: do I need termination, or is it something else?

Added 680 ohm bias at the Pi end and swapped to a proper twisted pair with a ground wire. 24 hours without a single timeout. I hadn’t even heard of biasing, thanks Laura. And no, I didn’t put 120 ohm on every meter.